{"product_id":"magfire-rate-of-rise-heat-detector-with-base-white","title":"MAGfire Rate of Rise Heat Detector With Base - White","description":"\u003ch5\u003eDescription\u003c\/h5\u003e\n\u003cp\u003eThe MAGfire RHD2 is a conventional rate-of-rise heat detector supplied with a mounting base, designed to trigger an alarm when ambient temperature exceeds 58°C or when temperature increases rapidly over a sustained period. Classified as A1\/R under EN 54-5, the detector uses a digital processing algorithm to distinguish between genuine fire conditions and brief temperature spikes from sources like radiators or direct sunlight.\u003c\/p\u003e\n\u003cp\u003eDesigned for installation in environments where smoke detectors would false-alarm, the RHD2 suits kitchens, boiler rooms, garages, workshops, and storage areas with high dust or steam levels. The low-profile white housing mounts directly to standard UK fire alarm back boxes via the included base, which provides both mechanical fixing and electrical connection to the fire panel circuit. The 360° visible LED on the detector head flashes every 8 seconds to confirm sensor status during routine inspection.\u003c\/p\u003e\n\u003cp\u003eThe detector's dual-mode sensing combines fixed-temperature and rate-of-rise detection in a single unit. Fixed-temperature sensing triggers at 58°C regardless of how slowly that temperature is reached, while rate-of-rise sensing triggers on rapid temperature increases that might not yet have reached the fixed threshold but indicate developing fire conditions. This dual approach reduces the time to alarm activation in fast-developing fires while maintaining reliable detection in slower thermal events.\u003c\/p\u003e\n\u003ch5\u003eSpecification\u003c\/h5\u003e\n\u003ctable class=\"spec_table\"\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Net Weight (KG)\u003c\/td\u003e\n\u003ctd\u003e0.08\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Gross Weight (KG)\u003c\/td\u003e\n\u003ctd\u003e0.09\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOuter Gross Weight (KG)\u003c\/td\u003e\n\u003ctd\u003e9\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOuter Length (mm)\u003c\/td\u003e\n\u003ctd\u003e360\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOuter Width (mm)\u003c\/td\u003e\n\u003ctd\u003e560\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOuter Height (mm)\u003c\/td\u003e\n\u003ctd\u003e320\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\n\u003ch5\u003eDownloads\u003c\/h5\u003e\n\u003cp\u003e\u003ca href=\"https:\/\/cdn.shopify.com\/s\/files\/1\/0729\/8993\/3835\/files\/products_RHD2_datasheet.pdf\" target=\"_blank\"\u003eProduct Specification Sheet\u003c\/a\u003e\u003c\/p\u003e\n\u003cp\u003e\u003ca href=\"https:\/\/cdn.shopify.com\/s\/files\/1\/0729\/8993\/3835\/files\/manual_RHD2.pdf\" target=\"_blank\"\u003eProduct Manual\u003c\/a\u003e\u003c\/p\u003e\n\u003ch5\u003eFrequently Asked\u003c\/h5\u003e\n\u003cp\u003e\u003cstrong\u003eWhat's the difference between rate-of-rise and fixed-temperature detection?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eFixed-temperature detection triggers when ambient temperature exceeds 58°C. Rate-of-rise detection triggers when temperature increases rapidly over a sustained period, even if the absolute temperature hasn't yet reached 58°C. The RHD2 combines both modes, so it activates on whichever condition is met first.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eWhere should heat detectors be used instead of smoke detectors?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eHeat detectors suit kitchens, garages, boiler rooms, workshops, and other environments where smoke, steam, dust or cooking fumes would cause false alarms with optical or ionisation smoke detectors. They respond to heat rather than particulates in the air.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eWhat does the flashing LED indicate?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eThe LED flashes every 8 seconds during normal operation to confirm the sensor is powered and functioning. This allows visual inspection of detector status without test equipment. In alarm condition, the LED behaviour changes as specified in the installation manual.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eIs the base included?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eYes. The RHD2 is supplied with a mounting base that fixes to a standard UK fire alarm back box and provides the electrical connection to the fire panel circuit. The detector head twists onto the base after wiring is completed.\u003c\/p\u003e","brand":"ESP","offers":[{"title":"Default Title","offer_id":45294083473675,"sku":"RHD2","price":10.99,"currency_code":"GBP","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0729\/8993\/3835\/files\/RHD2_a89607be-6d56-4326-aba7-98e3f84e0b75.jpg?v=1714667883","url":"https:\/\/niori.co.uk\/products\/magfire-rate-of-rise-heat-detector-with-base-white","provider":"Niori","version":"1.0","type":"link"}